Data Sheet 705021 Page 4/8
Electrical data
Case and ambient conditions
Approval/approval marks
Voltage supply
Connection Lateral (feed via base unit or router module)
Voltage DC 24 V +25/-20 %
Residual ripple 5 %
Current consumption 80 mA (at DC 19.2 V)
Power consumption 2 W
Inputs (terminals 1 to 18)
Connection At the front (removable terminal strips with Push-In technology)
Conductor cross section on terminals 1 to 18
Wire or strand without ferrule Min. 0.14 mm
2
, max. 1.5 mm
2
Strand with ferrule Without plastic collar: Min. 0.25 mm
2
, max. 1.5 mm
2
With plastic collar: Min. 0.25 mm
2
, max. 0.5 mm
2
Stripping length on terminals 1 to 18 9 mm
Electrical safety Acc. to DIN EN 61010-1
Overvoltage category III, pollution degree 2
Electromagnetic compatibility Acc. to DIN EN 61326-1
Interference emission Class A – only for industrial use –
Interference immunity Industrial requirements
Case type Plastic case for DIN rail mounting in the control cabinet (indoor use); DIN rail acc. to
DIN EN 60715, 35 mm x 7.5 mm x 1 mm
Dimensions (W x H x D) 22.5 mm x 103.6 mm x 101.5 mm (without connection elements)
Weight Approx. 125 g
Protection type IP20, acc. to DIN EN 60529
Ambient temperature range -20 to +55 °C
Storage temperature range -40 to +70 °C
Resistance to climatic conditions Relative humidity 90 % annual average without condensation (climatic class 3K3
acc. to DIN EN 60721-3-3 with extended temperature and humidity range)
Site altitude Up to 2000 m above sea level
Mechanical ambient conditions
a
a
Test conditions are listed in the System Descripton B 705000.8.
Classification acc. to DIN EN 60721-3-3, table 6, class 3M2
Approval mark Testing agency Certificate/certification
number
Inspection basis Valid for
c UL us Underwriters Laboratories E201387 UL 61010-1 (3. Ed.),
CAN/CSA-22.2
No. 61010-1 (3. Ed.)
all types